About UV Flame Detector
The Unit incorporates an extremely sensitive sensing circuit that responds to high energy sources in a bandwidth of 185 260 nm with optimum spectral sensitivity centred around 200 nm.
- Sensitive to virtually all fires including
Hydrogen and Hydrocarbon - Relay Output
- MODBUS (Optional)
- Virtually immune to:
1. Direct & reflected sunlight
2. Artificial Light source - Self-diagnosis including sensor check
- Ex-Proof
Specification
| Technology | UV IR |
| Model no. | UV-IR 250 |
| Response time | < 3 seconds |
| Adjustable Time Delay | 3 or 6 seconds |
| Cone of vision | 120 minimum |
| Optical Self-Test | Automatic continuous optical path |
| Input Power | 20-35 VDC, 125 mA standby, 230 mA alarm @ 24 VDC |
| Relay Contact Ratings | 2 amps @ 28 VDC or 300 VAC resistive |
| Alarm Reset | Automatic or manual when the flame is no longer detected |
| Communication | Available with optional MODBUS (RS-485) facility / HART |
| Operating Temperature | -40F to 185F (-40C to 85C) |
| Dimensions | 125 X 125 X 71 mm |
| Weight | Approx. 350 grams (Weather Proof) / Approx. 2 kg (Ex-Proof) |
| Compliance | EN 54-10, CCOE, SIL2, FM, ATEX, Vibration test |
Reliable Flame Detection for Plant SafetyOur UV Flame Detector provides critical safety assurance by monitoring plant environments for potential fire hazards. This device swiftly responds to UV radiation from flames, offering early alarm generation to prevent damage and ensure workplace safety.
User-Friendly and Customizable Alarm SystemDesigned for operational convenience, this flame detector includes a user-selectable alarm setting, allowing personnel to adjust parameters according to specific facility needs, thereby maximizing safety measures while minimizing false alarms.
FAQ's of UV Flame Detector:
Q: How does the UV Flame Detector improve plant safety?
A: The UV Flame Detector enhances safety by rapidly detecting ultraviolet radiation emitted from flames, enabling quick alerts and minimizing fire-related risks in plant environments.
Q: What features make this UV Flame Detector suitable for industrial applications?
A: Key features include a robust LM 6 construction, operation up to 60C, user-selectable alarm, and compatibility with a 24 V DC supply, ensuring reliable performance in rigorous plant settings.
Q: When should the UV Flame Detector be used in a facility?
A: This detector is ideal for continuous use in areas where fire risk management is critical, such as processing plants, storage facilities, and manufacturing units.
Q: Where can the UV Flame Detector be installed?
A: It can be mounted in plant safety zones, near critical machinery, or any location within industrial setups that requires flame detection and enhanced safety protocols.
Q: What is the process for configuring the user-selectable alarm?
A: Configuration involves accessing the alarm settings on the device and adjusting the sensitivity or alert type according to the specific needs of your facility, with guidance provided in the operation manual.
Q: What benefits does the UV Flame Detector offer compared to standard flame sensors?
A: This detector offers faster and more reliable flame recognition, reduced false alarms due to selectable response parameters, robust construction for industrial use, and a comprehensive 12-month warranty.